Tech
Notes 44B
- Wall Ties for Brick Masonry
[Revised May 2003]
Abstract:
The use of metal
ties in brick masonry dates back to loadbearing masonry walls in the 1850's.
Historically, the size, spacing and type of ties have been entirely empirical.
Over time, ties of various sizes, configurations and adjustability have been
developed for loadbearing masonry, cavity walls and brick veneer construction.
These ties are used to connect multiple wythes of masonry, often of different
materials; anchor masonry veneer to backing systems other than masonry; and
connect composite masonry walls. This Technical
Notes addresses the selection, specification and installation of wall tie
systems for use in brick masonry construction.
Information and recommendations are included which address tie
configuration, detailing, specifications, structural performance and corrosion
resistance.
Key
Words: anchors,
brick, cavity walls, corrosion,
design, differential movement, fasteners,
grout, masonry, structural
masonry, ties, veneer, walls.
INTRODUCTION
This Technical Notes is the third in a series that addresses anchor
bolts, fasteners and wall ties for brick masonry. This Technical Notes discusses wall ties commonly used in brick
construction, their function, selection, specification and installation. The
term "wall tie", as used in this Technical
Notes, refers to wire or sheet metal devices used to connect two or more
masonry wythes or used to connect masonry veneers to a structural backing
system. The later of these are more properly identified as veneer anchors.
GENERAL
The first
use of wall ties in brick masonry construction can be traced to England in the
mid-nineteenth century, where wrought iron ties were used in brick masonry
cavity walls. Use of wall ties in the United States grew after testing showed
that metal-tied walls were more resistant to water penetration than were
masonry-bonded walls. Bonders, or "headers", used in masonry-bonded
walls may provide direct paths for possible water penetration.
Testing also indicated that the compressive strength of metal-tied cavity
walls and solid walls, and the transverse strength of metal-tied solid walls
were comparable to those of masonry-bonded walls.
The use of
wall ties has continued to increase over the years due to a trend away from
massive, multi-wythe masonry walls to relatively thin masonry cavity walls,
double-wythe walls and veneers. The
use of backing systems other than masonry, i.e., steel, concrete and wood, has
rendered bonding with masonry headers impossible, leading to the development of
a number of different metal tie systems. Investigation
into the performance of masonry-bonded walls in which the bonded wythes are of
different materials indicates frequent shear failures in the headers.
During this period of
transition, little progress was made in the area of rational design of wall tie
systems. Typically, the sizing and
spacing of wall ties has been based largely on empirical information and the
designer's judgment. Questions concerning strength, stiffness, corrosion and the
effects of these on the long-term performance of wall ties, have been posed.
Selection of a tie system to function properly under these conditions is
further complicated by the vast number of tie types available and the variety of
materials from which they are fabricated. Most
tie systems perform well for their intended application.
Some tie systems, however, are poorly designed and do not provide
adequate load transfer for brick masonry. The
distinction is often subtle and requires an understanding of
the properties and characteristics of brick masonry. With the addition of Chapter 6 on Veneers to the Building
Code Requirements for Masonry Structures (ACI 530 / ASCE 5 / TMS 402-02),
the empirical requirements for type, size and spacing of metal ties have been
reviewed and refined. This Code,
known as the MSJC Code, contains requirements for most types of tie systems.
Function
of Wall Ties
Typically,
wall ties perform three primary functions between a wythe of brick and its
backing or another wythe of masonry: 1) provide a connection, 2) transfer
lateral loads, 3) permit in-plane movement to accommodate differential movements
and, in some cases, restrain differential movement.
In addition to these primary functions, metal ties (as joint
reinforcement) may also be required to serve as horizontal structural
reinforcement or provide longitudinal continuity.
For
a tie system to fulfill these functions, it must: 1) be securely attached to
both masonry wythes or the brick veneer and its backing, 2) have sufficient
stiffness to transfer lateral loads with minimal deformations, 3) have a minimum
amount of mechanical play, 4) be corrosion-resistant and 5) be easily installed
to reduce installation errors and damage to the tie system.
This listing is far from complete; special project conditions, unusual
details and special building code requirements must also be considered.
Availability and cost are always factors in product specifications. However, cost should not have a major influence on the
selection of a wall tie system since the cost of ties is typically a very small
part of the total wall cost.
TYPES
OF WALL TIES
General
There are a number of different wall tie systems available for brick masonry wall systems. These include unit ties, continuous horizontal joint reinforcement, adjustable ties (unit and continuous) and re-anchoring systems. Placement requirements for ties are shown in Figure 1.

FIG.
1
Unit
Ties
Unit ties are rectangular “box”ties, "Z" ties and corrugated ties, as shown in Figure 2. Rectangular and "Z" ties are usually fabricated from cold-drawn steel wire conforming to ASTM A 82. Rectangular and "Z" ties made of stainless steel conforming to ASTM A 580 are also available for use in more corrosive environments. Corrugated sheet steel ties are typically manufactured from steel sheet conforming to ASTM A 1008 and are also available in stainless steel conforming to A 240.

Unit
Ties
FIG. 2
Rectangular
and "Z" ties are used to bond walls constructed of two or more masonry
wythes. "Z" ties should
only be used to bond walls constructed with solid units (not less than 75%
solid) or grouted units. Rectangular
ties may be used with either solid or hollow units.
Such wire ties should not have a bend or drip to reduce water transfer.
Such a bend in the tie reduces the capacity of the tie to transfer
lateral load.
Corrugated
ties are typically used in low-rise, residential veneer over wood frame
construction and are not recommended for construction incorporating brick veneer
over steel studs, masonry-backed cavity walls, multi-wythe walls or grouted
masonry walls.
Typical installation details are shown in Fig. 3.

Unit
Tie Placement Details
FIG.
3
Joint
Reinforcement
Continuous
horizontal joint reinforcement is typically made from #8, 9, 10, or 11 gage
wire, or 3/16 in. (5 mm) diameter wire, conforming to ASTM A 951, in lengths of
10 to 12 ft (3 to 4 m). The most
common configurations are the ladder, truss, and tab types (see Fig. 4).
Continuous
Joint Reinforcement
FIG.
4
Structural
testing performed in the early 1960's indicated that multi-wythe walls tied with
joint reinforcement performed as well as walls tied with unit ties or masonry
bonders. Joint reinforcement may be
used in multi-wythe solid walls, masonry cavity walls, brick veneer with masonry
backing, and grouted masonry walls (see Fig. 5).
As with wire ties, the cross wires should be without drips.
Truss-type joint reinforcement is not
recommended for use in cavity walls or brick veneer with masonry backing. Test
results also indicated that truss-type joint reinforcement, in such wall
systems, did not contribute to any composite action in the vertical span, but
did develop a degree of composite action in the horizontal span .The
configuration of the truss diagonals can restrain differential movement between
wythes and possibly result in bowing of the walls.

Joint
Reinforcement Details
FIG. 5
Adjustable
Ties
Adjustable
tie systems were initially developed to accommodate the use of face brick whose
bed joints did not align vertically with interior masonry wythes.
This concept has been extended to ties used to attach brick to other
systems, resulting in the use of both adjustable unit ties and adjustable ties
with joint reinforcement.
The
use of adjustable ties has increased rapidly for a number of reasons:
1) Adjustable ties permit the construction of interior masonry wythes and
other backings prior to the construction of exterior facing wythes, permitting
the structure to be enclosed faster. 2)
Adjustable ties are two-piece systems. One
piece is installed as the backing is constructed and the other piece is
installed as the facing wythe is constructed, reducing the risk of damage to
exposed ties that might occur when unit ties or standard joint reinforcement are
used. 3) Adjustable ties can accommodate construction tolerances
common in multi-material construction. 4)
Adjustable ties can accommodate larger differential movements than standard unit
ties or joint reinforcement.
The
advantages offered by adjustable tie systems are not without possible problems:
1) Mislocation of adjustable ties placed prior to construction of facing
wythes, if extreme, can render the ties useless.
2) Adjustable ties may encourage less than perfect layout of the wall
system since a built-in adjustment allowance is available.
3) Large variations in construction tolerances may not allow full
engagement of ties installed before facing wythes are constructed. 4) Improperly positioned ties may result in large vertical
tie eccentricity. 5) The structural
performance of some adjustable ties in regard to strength and stiffness is less
than that of standard unit ties or joint reinforcement.
Adjustable Unit Ties. Adjustable unit ties produced for use with masonry backing, concrete backing, steel frames and steel studs are shown in Figs. 6 and 7. Slot-type ties (dovetail, channel slot, etc.) have been used for a number of years with concrete, steel frame and steel stud backing systems, and are recognized as tie systems capable of accommodating differential movement, as further discussed in Technical Notes 18 Series (see Fig. 6). Other types of adjustable unit tie systems are available for brick with masonry backing and other backing systems. These ties are typically two-piece systems, consisting of a single or double eye and pintle arrangement (see Fig. 7). The Building Code Requirements for Masonry Structures (ACI 530 / ASCE 5 / TMS 402-02) requires that for veneer masonry all pintle anchors have at least two pintle legs of wire size W2.8 (3/16 in., MW18) each and have an offset not exceeding 1 ¼ in. (31.8 mm). Typical installation details are shown in Fig. 8
.
Adjustable
Unit Ties for Steel, Concrete and Stud Backup
FIG.
6

Adjustable Unit Ties for Masonry Backup
FIG. 7

Adjustable
Unit Tie Details
FIG.
8
Adjustable Assemblies. Adjustable ladder and truss-type joint reinforcement assemblies are available for use in masonry backed-cavity wall, veneer and grouted wall construction. This joint reinforcement typically consists of rectangular tab type extensions, connected to standard joint reinforcement by means of an eye and pintle arrangement (see Fig. 9). Installation details are shown in Fig. 10.

Adjustable Joint Reinforcement Assemblies
FIG. 9

Adjustable
Assembly Details
FIG. 10
|
Masonry
Re-anchoring Systems. Masonry re-anchoring systems are the most recent development in masonry tie systems. Three general types of systems are being produced and typically consist of a mechanical expansion system, helical screw system and an epoxy adhesive system (see Fig. 11).These systems are primarily used to: provide ties in areas where ties were not installed during original construction, 2) replace existing ties, 3) replace failed masonry bonding units, 4) upgrade older wall systems to current code levels, or 5) attach new veneers over existing facades.
|

Masonry Re-Anchoring Systems
FIG. 11
As stated, re-anchoring systems
are relatively new and many designers and contractors may not be fully familiar
with their installation or limitations. For this reason, consultation with the
tie system manufacturer is essential to assure proper application, detailing,
installation, inspection, and performance.
TIE
SELECTION
Strength
and Deformation
The strength
and deformation characteristics of tie systems are not generally analyzed nor
investigated during the project design or specification phase.
Building codes and standards have typically required minimum tie size
(diameter or gage) and maximum tie spacing limits to control tie loading and
deformation. Present tie size and
spacing requirements have been derived from some testing and from the past
performance of traditional tie systems (rectangular ties, "Z'' ties and
standard joint reinforcement). The
growing use of adjustable tie systems has caused some concerns in regard to tie
strength and deformation. Most
adjustable ties permit vertical adjustment up to approximately one-half the
height of a standard brick unit, some permit greater adjustments.
Depending on the tie configuration, the deflections of adjustable ties
can become quite large as vertical adjustment eccentricities are increased. This deflection is further increased if mechanical play is
present in the tie system.
Analytical
and experimental investigations of cavity wall and veneer wall systems have
shown that tie loads and deformations are a function of:
1) the relative stiffness between facing and backing materials, 2) tie
spacing, 3) tie stiffness, 4) support conditions of the facing and backing
systems, 5) location of edges and openings, 6) cavity width and 7) applied
loads.
Estimating tie loads based on tributary area can lead to large errors, depending on the geometry and properties of the wall system. Fig. 12 shows tie loads and deflections calculated from a simplified model of a cavity wall system. As shown, adjustable tie deflections become large as the adjustment eccentricity becomes large. These values were calculated assuming that no mechanical play existed in the tie system. Mechanical play must be added to these values to determine the total deflection of the exterior wythe. Typical adjustable ties have values of mechanical play ranging from approximately 0 to 0.3 in. (0 to 8 mm). Some adjustable ties may have an extreme amount of mechanical play when not properly installed (see Fig. 13). The MSJC Code limits mechanical play to a maximum of 1/16 inch (1.6 mm). If satisfactory performance is to be expected, total tie and backing deflections must be maintained within the working range of the masonry facade under full design loads.

Calculated Tie Loads and Deflections
FIG. 12

Mechanical Play
FIG. 13
Recommendations. At present, analysis
techniques that accurately model metal-tied wall systems are still in the
developmental stage and require further refinement and verification through
testing. Until more accurate
methods are available, the Brick Industry Association feels that acceptable
strength and deformation characteristics can be achieved by one or more of the
following measures: 1) Reduce or
eliminate lateral mechanical play in adjustable tie systems.
Limit the total mechanical play to 1/16 in. (1.6 mm), see Fig. 13.
2) Reduce or eliminate adjustment eccentricity in adjustable tie systems.
This can be accomplished by installing ties as facing wythes are constructed or
by using starter courses or ledges when facing wythes are constructed over
masonry backing. 3) Eliminate
possible disengagement of adjustable ties by providing positive vertical
movement limitations. 4) Provide
additional ties within 8 in. (200 mm) of openings and discontinuities, i.e.,
windows, shelf angles, vertical expansion joints, etc. 5) Do not specify ties
with formed drips. Testing has
shown that drips can reduce the ultimate buckling load by approximately 50
percent. 6) Space ties as shown in Table 1, based on the tie system
and wall system. 7) Specify stiff
ties. This can be accomplished by
specifying ties with maximum deflections of less than 0.05 in. (1.2 mm) when
tested at an axial load of 100 lb in tension or compression.
When adjustable ties are specified, the deflection limit should be
satisfied at the eccentricity expected in the field.
See Table 2 for minimum tie gage and diameter recommendations.
8) Select an appropriate tie system for the wall system (see Table 3).
Many of these recommendations have been incorporated in the MSJC Code.

2.
Based on the requirements in the 2002 MSJC Code.
3.
Maximum allowable distance between inside face of veneer and framing
material, per MSJC Code, unless noted otherwise.
TABLE 2
Required
Tie Sizes1

1 Based on the requirements in the 2002 MSJC Code.

1See Table 1
for spacing; Table 2 for sizes and gages; Table 5 for corrosion protection.
Corrosion
General. Awareness of
possible corrosion problems in metal-tied masonry walls has increased due to
corrosion damage found on reinforcement in concrete highway pavements, bridge
decks and some masonry structures.
The potential for corrosion problems in masonry has increased as
construction and design philosophies have changed and as environmental
conditions have changed over the last decades.
These changes include use of thinner masonry walls and masonry veneers
that are more susceptible to water penetration, increases in atmospheric
pollutants, use of accelerators containing calcium chloride, increased use of
insulated cavities (resulting in the relocation of the dew point within the wall
section) and combinations of different metals in brick veneer wall systems.
This list is not all-inclusive; corrosion potential can also be affected
by the function of a structure, geographic location, compatibility of
construction materials, detailing and workmanship.
Corrosion Protection. In
order to provide corrosion protection, environmental factors must be controlled
or metals used in construction must be protected.
Conventional corrosion protection methods attempt to protect metals
embedded in masonry by isolating them with impervious coatings (barrier
protection), by using metals that are corrosion-resistant, or by providing
cathodic protection in which one metal becomes sacrificial to protect another.
Galvanizing — Galvanizing
(zinc-coating) provides resistance to corrosion by two methods.
First, the zinc coating acts as a barrier shielding the underlying steel
from corrosive action. Second, it acts as a sacrificial element that is consumed
before the base steel is attacked. This
sacrificial nature protects the base steel at scratches and discontinuities in
the zinc coating caused by fabrication, handling or installation, until most of
the adjacent zinc coating is consumed. Studies
have shown that the protective value of zinc coating is proportional to its
thickness. Thus, for longer periods
of protection, a thicker zinc coating is required.
Also, when the protective zinc coating is depleted, the corrosion of the
base steel will progress as if no galvanizing were present.
Two methods
of galvanizing are used to protect metal masonry ties:
mill galvanizing and hot-dip galvanizing.
Mill galvanizing takes place after steel wire or sheets have been
processed to their specified dimensions and prior to fabrication of the tie. During the mill galvanizing process, zinc can be applied in a
variety of thicknesses, as shown in Table 4.
Hot-dip galvanizing is performed by dipping completely fabricated
assemblies into molten zinc until a specified amount of zinc is bonded to the
base metal. Hot-dip galvanized
coatings are typically thicker than mill galvanized coatings and therefore,
provide longer periods of protection.
TABLE 4
Coating Requirements

1Class B —
Rolled, pressed or forged articles.
B-1: 3/16 in. (4.8 mm) and over in thickness and over 15 in. (381 mm) in
length
B-2:
Under 3/16 in. (4.8 mm) in thickness and over 15 in. (381 mm) in length.
B-3:
Any thickness and 15 in. (381 mm) and under in length.
Stainless Steel - Stainless steel
ties are often specified for use in very corrosive environments.
Stainless steel ties are specified under ASTM A 240 or A 580 and are
generally made from one of the austenitic stainless steels.
Stainless steel resists corrosion well; however, if in contact with
carbon steel, a galvanic cell can result and actually increase the potential for
corrosion. For this reason,
combining stainless steel ties or screws with carbon steel or galvanized steel
components is not recommended.
Fusion-Bonded Epoxy — Epoxy coating is the newest process used to provide corrosion
protection for metal ties. The
process has been adapted from epoxy-coated reinforcement bars used successfully
in concrete systems with severe environmental exposures. Epoxy coating provides protection by acting as an impervious
barrier. The epoxy coating is
bonded to the base steel by a heat-induced chemical reaction through which a
chemical and mechanical bond is formed. The
combination of the two types of adhesion helps to prevent cracking of the
coating due to handling, installation or stress reversals.
The epoxy coating is not sacrificial like zinc; therefore, nicks and
voids in the coating can lead to corrosion of the base steel.
Epoxy coatings for joint reinforcement should meet the requirements of
ASTM A 884, Class A, Type 1 - 7 mils. Epoxy
coatings for wire ties and anchors are specified in ASTM A 899, Class C - 20
mils. Sheet metal ties and anchors
should be coated with 20 mils of epoxy per surface or per manufacturer's
specification.
Recommendations.
The past
performance of metal ties in regard to corrosion has generally been
satisfactory. The American
Galvanizers Association has developed a Zinc Coating Life Predictor program that
provides an estimate of service life for zinc coating in an exposed environment.
This does not specifically address performance of ties in masonry walls.
Until research can produce accurate methods of assessing corrosion
potential and predicting adequate levels of protection, the Brick Industry
Association suggests minimum levels of corrosion protection for metal ties and
hardware as indicated in Table 5. As
with all other engineering considerations minimum recommendations may not be
adequate in every situation, and should not serve as substitutes for engineering
investigation or judgment. Decisions
must be based on individual project conditions, performance requirements and
safety.
TABLE
5
Recommended Minimum Corrosion Protection

SUMMARY
This Technical
Notes is the third in a series addressing brick masonry anchor bolts,
fasteners and wall ties. It is
primarily concerned with the types of wall ties commonly used in brick masonry
construction, their function, selection, specification and installation.
Other Technical Notes in this
series individually address anchor bolts and fasteners for brick masonry.
The information and suggestions contained in this Technical Notes are based on the available data and the experience
of the engineering staff of the Brick Industry Association.
The information contained herein must be used in conjunction with good
technical judgment and a basic understanding of the properties of brick masonry.
Final decisions on the use of the information contained in this Technical Notes are not within the purview of the Brick Industry
Association and must rest with the project architect, engineer and owner.
REFERENCES
1.
DeVekey, R.C., ''Corrosion of Steel Wall Ties: Recognition, Assessment
and Appropriate Action”, Building Research Establishment Information Paper, IP
28/79, Building Research Establishment, Garston, Watford, England, October 1979.
2.
Fishburn, C.C., ''Water Permeability of Walls Built of Masonry Units”,
Report BMS 82, National Bureau of Standards, Department of Commerce, Washington,
D.C., April 1942.
3.
Allen, M. H., Research Report No. 10, “Compressive and Transverse
Strength Tests of Eight-Inch Brick Walls”, Structural Clay Products Research
Foundation, Geneva, Illinois, October 1966.
4.
Allen, M.H., Research Report No. 14, “Compressive Strength of
Eight-Inch Brick Walls with Different Percentages of Steel Ties and Masonry
Headers”, Structural Clay Products Research Foundation, Geneva, Illinois, May
1969.
5.
Bortz, S.A., “Investigation of Continuous Metal Ties as a Replacement
for Brick Ties in Masonry Walls”, Summary Report ARF 6620, Armour Research
Foundation, Chicago, Illinois, June 1960.
6.
”Investigation of Masonry Wall Ties”, ARF Project B870-2 (Revised),
Armour Research Foundation, Chicago, Illinois, December 1962.
7.
''Flexural Strength of Cavity Walls”, ARF Project B870, Armour Research
Foundation, Chicago, Illinois, March 1963.
8.
Brown, R.H. and Elling, R.E., ''Lateral Load Distribution in Cavity
Walls”, Proceedings of the Fifth International Brick Masonry Conference,
Washington, D.C., October 1979.
9.
Bell, G.R. and Gumpertz, W.H., ''Engineering Evaluation of Brick
Veneer/Steel Stud Walls, Part 2 —Structural Design, Structural Behavior and
Durability”, Proceedings of the Third North American Masonry Conference,
Arlington, Texas, June 1985.
10.
Arumala, J.O. and Brown, R.H., ''Performance of Brick Veneer With Steel
Stud Backup”, Clemson University, Clemson, South Carolina, April 1982.
11.
''Development of Adjustable Wall Ties”, ARF Project No. B869, Armour
Research Foundation, Chicago, Illinois, March 1963.
12.
Catani, Mario J., ''Protection of Embedded Steel in Masonry”, The
Construction Specifier, January 1985.
13.
Catani, Mario J. and Whitlock, A. Rhett, ''Coping With Wide Cavities”, The
Construction Specifier, August 1986.
14.
Zhang, X. Gregory, Zinc Coating Life Predictor, The International Lead Zinc Research
Organization, published online at http://zclp.galvanizeit.org:8180/zclp/index.html,
2002.